Adjustable thermostatic and pressure
balanced mixing valve for point of
distribution in domestic water systems
and radiant hydronic heating systems.
Low-lead brass body.
Internal anti-scale materials.
Locking set point knob.
Max. working pressure: 200 psi.
Max. inlet temperature: 200ºF.
Adjustable range: 85—150ºF.
Gauge scale: 30—210ºF.
Gauge accuracy: ± 6ºF.
Gauge dial: 2" diameter.
ASSE 1017 Listed.
Lead Plumbing Law Compliance:
(0.25% Max. weighted average lead
content).
Lead Plumbing Law Certified by
IAPMO R&T.
Two-way on/off two position valve.
Straight through flow pattern.
Brass body.*
Stainless steel stem.
EPDM rubber seals and paddle.
Max. working pressure: 300 psi.
Max temperature: 240°F.
*Agency Approval for low-lead brass body:
Lead plumbing law compliance: (0.25 max.
weighted average lead content).
Lead plumbing law certified by IAPMO R&T
Two-way on/off two position valve.
Straight through flow pattern.
Brass body.*
Stainless steel stem.
EPDM rubber seals and paddle.
Max. working pressure: 300 psi.
Max temperature: 240°F.
*Agency Approval for low-lead brass body:
Lead plumbing law compliance: (0.25 max.
weighted average lead content).
Lead plumbing law certified by IAPMO R&T
Three-way on/off two position valve.
Diverting flow pattern.
Brass body.
Stainless steel stem.
EPDM rubber seals and paddle.
Max. working pressure: 300 psi.
Max temperature: 240°F.
*Agency Approval for low-lead brass body:
Lead plumbing law compliance: (0.25 max.
weighted average lead content).
Lead plumbing law certified by IAPMO R&T.
Caleffi 3-Way Diverting Valve with 1" Sweat Connections
Three-way on/off two position valve.
Diverting flow pattern.
Brass body.
Stainless steel stem.
EPDM rubber seals and paddle.
Max. working pressure: 300 psi.
Max temperature: 240°F.
*Agency Approval for low-lead brass body:
Lead plumbing law compliance: (0.25 max.
weighted average lead content).
Lead plumbing law certified by IAPMO R&T.
Air separator with automatic ½" check
valve (code 561402A) to mount expansion
tank on bottom thread.
Brass body.
Glass reinforced nylon internal element.
Max. working pressure: 150 psi.
Working temperature range: 32—250°F.
In heating and air conditioning control systems, the circulation of water containing impurities may result in rapid wear and damage to components such as pumps and control valves. It also causes blockages in heat exchangers, heating elements and pipes, resulting in lower thermal efficiency within the system. The dirt separator separates off these impurities, which are mainly made up of particles of sand and rust, collecting them in a large collection chamber, from which they can be removed even while the system is in operation. This device is capable of efficiently removing the smallest particles, with low head loss.
1" NPT Inlet Ball valves and 3/4" outlets. This pre-assembled distribution assembly with Return distribution manifold including Built-In Shut-Off Valves suitable for Thermo-Electric Actuators, and Supply distirbution manifold including Manually-Adjustable Balancing Valves. MAX working pressure: 150 psi. MAX temperature 210 F.
Distribution manifolds for radiant panel systems are used to optimally distribute the heating fluid in floor
heating system circuits and ultimately improve the control of heat emission from the panels. The manifolds
ensure that the flow of each circuit is regulated precisely and also control the shut-off, venting and automatic
removal of air from the system.
680 series fi ttings are compatible with any
ASTM F876 single layer PEX.
Max. working pressure: 150 psi.
Working temperature for ASTM F876 PEX
piping: -41—180°F.